Thermal camera • SN 1
UNI 730

Infrared scan of live electrical boards. Loose terminals, overload and busbar heating are imaged before C1/C2 fire risk; thermograms are attached to the report.

Instrument specifications

Maker / model UNI-T · UTi730E (UNI 730)
Class Handheld thermal imager
IR resolution 320 × 240
Visual camera 2 MP; fusion / PIP
Display 3.5″ IPS, 640 × 480
NETD ≤ 65 mK
FOV 56° × 42°
Range −40 °C … 400 °C
Accuracy ±2 °C or ±2 %, whichever is greater
Frame rate ≤ 25 Hz
Rating IP54, 2 m drop
Output Radiometric JPEG, Type-C, microSD
Asset SN 1

Ministry mandatory items and coverage

  • ZPKR02 visual inspection is supported by thermography: board hotspots, terminals and busbars are attached as evidence.
  • Work Equipment Regulation art. 14/B and fire-licence / insurance renewals often require a thermography annex.
  • ΔT 1–10 °C: early heating — tightness and cleaning at planned maintenance.
  • ΔT 10–20 °C: medium risk — check or replace breaker / terminal.
  • ΔT > 20 °C: critical (C1 / C2) — fire risk; stop and repair.
  • The scan is live; production is not stopped.
  • C1 means the installation is not fit for use; C2 urgent, C3 by the next period.

Related article → Elektrik Panolarında Termografik (Termal Kamera) Muayene ve Arıza Önleme