Back to docs

Sonel MPI-540

Installation tester • SN 11 • Cal 233
Sonel MPI-540

Multifunction installation tester for earthing, loop impedance, RCD and insulation on LV systems. Numerical values in ZPKR reports are taken with this calibrated instrument.

Instrument specifications

Maker / model Sonel S.A. · MPI-540
Class Multifunction installation tester (IEC 61557)
Display 7″ TFT touch, 800 × 480
Rating IP51 · CAT III 500 V / CAT IV 300 V
Loop impedance ZL-PE, ZL-N, ZL-L; Zs without tripping RCDs
RCD AC / A / B; trip current IA and time tA
Insulation 50 / 100 / 250 / 500 / 1000 V
Earthing 3- and 4-pole, clamp, soil resistivity
Continuity PE / bonding, 200 mA
Power quality EN 61000-4-30 class S, 3-phase recorder
I/O USB, Wi-Fi, Bluetooth, microSD
Asset SN 11 · Calibration no. 233

Ministry mandatory items and coverage

  • Work Equipment Regulation art. 14/B: electrical periodic inspection at least yearly by an authorised electrical / electronics engineer.
  • From 01.09.2025 the ÇSGB ZPKR format must be used in full form and content; legacy formats are invalid.
  • ZPKR01 — LV earth resistance, loop impedance, PE / bonding continuity.
  • ZPKR02 — Function tests: 30 mA RCD trip current and time on socket circuits up to 32 A.
  • ZPKR03 — Lightning down-conductor and earth resistance (TS EN 62305).
  • ZPKR05 — Transformer 1–36 kV body / neutral earth resistance.
  • Cable–breaker coordination Ib < In ≤ Iz; board Icu must not be below the calculated 3-phase short-circuit current.
  • The calibration certificate is attached to the report. C1 immediate, C2 urgent, C3 improvement.